Type: KM50-C intelligent monitor.
Application circuit: single phase 2 wire system AC100 ~ 240V; single phase 3 wire system AC100/200V;
Three-phase 3 wire system AC100 ~ 240V.
Power supply voltage sharing: sharing AC100 to 240V with the measured voltage input.
Shape: 48 (H) * 48 (W) * 84 (D).
Communication: RS-485.
Protocol: ompoWay/F: the number of communication nodes 31 Modbus: the number of communication nodes 99 (shared).
Energy classification function (industry initiative).
Show the 3-STATE function through the 3 color display energy saving room for improvement.
Equipped with easy to grasp the room for energy saving and convenient 3-STATE function.
3-STATE function refers to the use of the state power, the cumulative power is divided into operation / standby / stop 3 types of functions.
2 and 3-STATE function linkage, can operate / standby / stop 3 points for individual output
Pulse input count, pulse input ON time, unit power consumption measurement.
Product name: Split type CT, Connector: For connecting the branch cable,
Cable length: 0.2 m.
Power supply: Battery/DC cable.
Easy and Quick "Checking Power"at the Worksite. Application: 410 × 410 mm.
Power supply: 24 VDC.
The ZN series is even thinner and,
sports improved air volume.
These products enable cleaning that,
is both fast and flexible OMRON KM50-C1-FLK.
Three sizes are available to match various sizes of clean booths
KM50-C1-FLK Item (Measured particle diameter): Air Thermo Sensor,
For temperature / humidity measurement.
Make your entire production environment visible.
Multi-point monitoring of environmental data and central control. Product name: Branch cable (cable length 1.3 m).
Power supply: Battery/DC cable OMRON KM50-C1-FLK.
Easy and Quick "Checking Power"at the Worksite. Appearance: Sensor head: Anchored type.
Temperature: Measurement range, 0 to 60°C;
Measurement precision, ±0.3°C (at 25°C); Resolution, 0.1°C.
Relative humidity: Measurement range, 20 to 85%;
Measurement precision, ±2.5% (at 25°C, 10 to 85%); Resolution, 0.1%.
Weight (packaged): Approx. 300 g.
Accessories: Mounting screw (M3 x 8) x 1 Caps to secure cable,
(one for each, front and rear) OMRON KM50-C1-FLK.
Easy temperature and humidity control with an SD Card. Type: related equipment (sold separately); split type current transformer (CT).
Rated primary side current: 250A.
Rated two secondary current: 1A.
Simple monitoring of the use of electricity to support energy saving countermeasures.
On behalf of the use of the mechanical equipment, the measurement of the initial voltage, current,
Cumulative quantity, invalid power, power factor, frequency.
To achieve a simple record with a memory card. (with memory card function model)
The measurement data can be stored in the main body, and the centralized monitoring and management can be carried out in the communication network.
Wide 45mm miniaturization, simple set to the DIN guide. Easy temperature and humidity control with an SD Card. Rated primary current: 100 A.
Rated secondary current: Special output.
Installation: Installed separately.
High-performance Power Monitor Suitable for On-panel Mounting and Display.
Assists Energy-saving Analysis.
Energy classification for wasted standby and stopped power.
(Classification based on external inputs is also supported.)
Power and current can be measured simultaneously.
Measurement of flow rates with a pulse conversion function.
Simple temperature measurements with Temperature Sensor included in the Unit.
High-precision Measurements.
Measurement of generated power (regenerative power),
leading reactive power, lagging reactive power, and consumed power.
Power measurements on the primary side of inverters,
which are widely used to save energy.
Automatic range switching for accurate measurement of standby and stopped power.
Energy-saving Functions.
Conversion to monetary cost. (Also used for classified standby and stoppedd power KM50-C1-FLK. )
Alarm outputs can be selected for active power, reactive power,
regenerative power, current, voltage, or power factor.
The Power Monitor can log measurement data and supports Modbus communications.
Installation and Settingss KM50-C1-FLK.
Direct measurement of three-phase, four-wire, 400-V line voltage.
Simple measurements without voltage wiring.
Incorrect voltage wiring detection.