Internal I/O common: PNP.
I/O indicators: LED display (yellow).
Unit power supply current consumption: 120 mA max.
e-CON Connector insertion durability: 50 times.
Weight: 140 g max.
Expansion functions: No.
e-CON connectors.
Special wiring tool is not necessary.
standard e-CON connectors.
each connector.
be connected directly.
high-speed processing.
switch and with tool software.
becomes possible for maintenance.
Name: Expansion Units.
Specifications: Outputs;
8 outputs; PNP;
One Expansion Unit can be,
mounted to one CRT1-ID16(-1),
CRT1-OD16(-1), CRT1-ROS16,
or CRT1-ROF16 Digital I/O Slave.
Standards: CE, UC, UC1, N.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet OMRON GX-MD1628.
Wiring material cost can be reduced.
Bit-level I/O distribution reduces,
wiring in the system
GX-MD1628
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on site.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error OMRON GX-MD1628. I/O classification: Input.
Internal I/O circuit common: NPN (+ common).
I/O points: 16.
Rated voltage: 24 VDC.
I/O rated voltage: 24 VDC.
Module Type that Allows PCB Mounting.
Compact size at 60 x 16 x 35 (W x H x D).
Lineup now includes the 16-point input model and,
16-point output model. Input capacity: 16 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min OMRON GX-MD1628.
(between each input terminal and the V terminal)
OFF voltage: 5 VDC max.
(between each input terminal and the V terminal)
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms, 1 ms,
2 ms, 4 ms, 8 ms, 16 ms, 32 ms. (Default setting: 1 ms)
Number of circuits per common: 8 points/common.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Input device supply current: 100 mA/point.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current consumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 370 g max.
Expansion functions: No.
Short-circuit protection function: No.
A common terminal is provided for each contact.
It eliminate the needs for relay terminal blocks.
It is unnecessary to share the common terminal,
among mulltiple contacts GX-MD1628.
Easy-to-find wiring locations.
Detachable screw terminal block facilitates the maintenance.
Input response time can be switched for high-speed processing.
Selectable node address setting methods: setting with rotary,
switch and with tool software GX-MD1628.
When setting the nodes with rotary switch, setting is easy and,
node identification becomes possible for maintenance.