OMRON
Home >> Products >> OMRON >> Master slave station products >> EtherCAT remote I/O terminal >> GX-ID3218 | OMRON Digital I/O Terminal 3-tier Terminal Block Type GX-ID3218

GX-ID3218 | OMRON Digital I/O Terminal 3-tier Terminal Block Type GX-ID3218

OMRON GX-ID3218 Manual And Instructions
GX-ID3218 datasheetPDF datasheet
GX-ID3218 PROGRAMMING MANUAL
GX-ID3218 INSTRUCTION MANUAL

OMRON GX-ID3218 Product information and technical parameters:
Brand: OMRON
Name: Digital I/O Terminal 3-tier Terminal Block Type
Model: GX-ID3218
Input capacity: 32 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min. (between each in,
put terminal and the V terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the V terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 32 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 230 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 220 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common terminal is provided for,
each connector.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance.

Specifications: Outputs, NPN(- common), 32 outputs.
I/O connections: MIL connector.
Rated internal circuit power supply voltage:
Supplied from communications connector.
Rated I/O power supply voltage: 24 VDC.
First Board-type Terminals for Smart Slaves!
Easily modified to handle an array of I/O interfaces,
and eliminates much on-site wiring OMRON GX-ID3218.
User boards attach easily to the DRT2-@D32BV(-1) using screws GX-ID3218 Name: MIL Connectors.
Specifications: Inputs;
32 inputs ; NPN; --.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring material cost can be reduced.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction OMRON GX-ID3218.
Seven-segment Display on the Gateway Unit,
helps to detect errors on site.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error. Specifications: Outputs, PNP (+ common), 4 points.
I/O connections: Sensor I/O connector.
Rated internal circuit power supply voltage:
Supplied from the communications OMRON GX-ID3218. connector.
Rated I/O power supply voltage: 24 VDC.
Remote I/O Terminals with High.
Degree of Environmental Resistance.
(IP67) in Product Lineup Including.
Economical Input, Output, and Mixed I/O Models.
Common Smart Slave functionality provides strong support for equipment,
operation status monitoring and effective maintenance.
High degree of environmental resistance with dust-proof and drip-proof,
construction. (IP67)
Models with one connector for two outputs are available to make easier,
connection with hydraulic valve devices.
(Models with 16 outputs and models with 16 mixed I/O)Input capacity: 32 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min. (between each in,
put terminal and the G terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the G terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 32 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 230 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 220 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A commonn terminal is provided for,
each connector GX-ID3218.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
sswitch and with tool software GX-ID3218.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance.