Classification: LED indicator.
Coil ratings: AC 24, 110, 120, 230, 240; DC 6, 12, 24, 48.
Contact form: SPDT.
Slim and Space-saving Power Plug-in Relay.
Reduces wiring work by 60% when combined with the,
P2RF-@-PU Push-In Plus Socket.
(according to actual OMRON measurements).
Lockable test button models available G3J-S405BL INSTRUCTION MANUAL.
Built-in mechanical operation indicator.
Provided with nameplate
G3J-S405BL
AC type is equipped with a coil-disconnection self-diagnostic,
function (LED type).
High switching power (1-pole: 10 A). Input terminals: Screwless clamp terminals (detachable).
Isolation method: Phototriaccoupler.
Zero cross function: Yes.
Operation indicator: Yes.
Alarm output: 2 outputs (Heater Burnout Detection,
SSR Short-circuit Failure Detection) G3J-S405BL INSTRUCTION MANUAL.
Applicable load (See note.): 2 to 35 A, 100 to 240 VAC.
A New-concept SSR with Built-in.
Current Transformer.
Heater Burnout and SSR Short.
circuit Failure Detection.
Built-in Current Transformer (CT) helps reduce wiring steps.
Detects the burnout of any one of a group of heaters.
Detects the burnout of 3-phase heaters.
Detects SSR short-circuit failures G3J-S405BL INSTRUCTION MANUAL.
Error detection level can be easily set with a switch.
Mounts to a DIN track or with screws.
Three types of input terminals available: M3 terminals,
screwless clamp terminals (detachable), or compact slotted,
screw terminals (detachable).
Certified for CSA and EN (TÜV).
The G3PF-2@@B-@@@ Series is UL certified. Isolation: Phototriac coupler.
Zero cross function: Yes.
Indicator: Yes.
Rated output load: 10 A at 24 to 240 VAC.
Rated input voltage: 5 to 24 VDC.
Extremely Thin Relays Integrated with Heat Sinks.
Downsizing achieved through optimum design of heat ssink G3J-S405BL Manual.
Mounting possible via screws or via DIN track.
Close mounting possible for linking terminals.
(Except for G3PA-260B-VD and G3PA-450B-VD-2.)
Applicable with 3-phase loads.
Replaceable power element cartridges.
Comply witth VDE 0160 (finger protection),
with a dielectric strength of 4,000 V between input and load G3J-S405BL Manual.
Certified by UL, CSA, and VDE (reinforced insulation).