OMRON
Home >> Products >> OMRON >> Temperature controller >> Universal temperature controller >> E5CC-RX3ASM-004 | OMRON Digital temperature controller E5CC-RX3ASM-004

E5CC-RX3ASM-004 | OMRON Digital temperature controller E5CC-RX3ASM-004

OMRON E5CC-RX3ASM-004 Manual And Instructions
E5CC-RX3ASM-004 RS-485 CompoWay/Flnstruction Manual
E5CC-RX3ASM-004 INSTRUCTION Manual

OMRON E5CC-RX3ASM-004 Product information and technical parameters:
Brand: OMRON
Name: Digital temperature controller
Model: E5CC-RX3ASM-004
Size: 48 x 48mm.
Control output 1: relay output.
Control output 2:--.
Auxiliary output: 3 points (common universal).
Power supply voltage: AC100 ~ 240V.
Terminal type: screw terminal table type.
Input category: full range multi input.
Heater break, SSR fault detection function: -.
Communication: RS-485.
Event input: 2 points.
Remote SP input: -.
Transfer output: -.
Using large font PV display (white), improve visibility.
Selection, operation and setting.
Functional performance of input and output points.
Support for more extensive range of applications.
Using high PV 15.2mm display (white), improve visibility.
High speed sampling to achieve 50ms.
With auxiliary output (maximum 3 points), event input (maximum 4 points), the transmission output,
Remote SP input function, support for a variety of applications.
E5CC 60mm has a depth of slender body.
The use of communication adapter cable (sold separately) connected with a computer.
After that, no power supply connection can be set.
It can be easily set by CX-Thermo (sold separately).
Easy to connect with PLC through no program communication.
Combined temperature control device through component communication.

E5AR Digital Controllers offer high speed,
high precision, and multiple I/O and use a 5-digit,
3-row LCD display for high visual.
clarity.
A short sampling period of 50 ms enables use in applications,
requiring high-speed response.
PV, SP, and MV data is displayed simultaneously in a 3-row,
negative LCD display with a backlight OMRON E5CC-RX3ASM-004.
Multiloop control, cascade control, and proportional control are,
possible with a single Controller E5CC-RX3ASM-004
When using models with CompoWay/F communications, initial,
settings can be downloaded and settings can be masked using,
Support Software (CX-Thermo version 4.0 or higher).
Equipped with calculation functions as a standard (e.g., square,
root calculation and broken-line approximation) OMRON E5CC-RX3ASM-004.
DeviceNet Communications.
Data setting and monitoring can be performed without special,
programming. Case color: Black.
Control output: Relay output.
Control mode *1: Standard or heating/cooling.
No. of auxiliary outputs: 2.
Detection of heater burnout, SSR failure, and heater overcurrent:
Detection for single-phase heaters.
No. of event inputs: --.
Transfer output *2: -- OMRON E5CC-RX3ASM-004.
Communi cations: --.
Previous model: Thermocouple input, --;
Resistance thermometer input, --.
New 48 x 24-mm Basic Temperature,
Controller with Enhanced Functions and,
Performance. Improved Indication Accuracy,
and Preventive Maintenance Function.
Indication Accuracy.
Thermocouple input: ±0.3% of PV (previous models: ±0.5%),
Pt input: ±0.2% of PV (previous models: ±0.5%),
Analog input: ±0.2% FS (previous models: ±0.5%),
Models are available with screw terminal blocks or screwless,
clamp terminal blocks.
A PV/SV-status display function can be set to automatically alternate,
between displaying the status off the Temperature Controller (auto/
manual, RUN/STOP, and alarms) and the PV or SV E5CC-RX3ASM-004.
Preventive maintenance for relays in the Temperature,
Controller using a Control Output ON/OFF Counter.
Switch the PV display between three colorrs E5CC-RX3ASM-004.
Compatible with Support Software (CX-Thermo version 4.2 or higher).
Eleven-segment displays.
Models are available with one or two alarm outputs.