Terminal type: Exposed-lead Models.
Protective tubing diameter D (mm): 6.4 dia. .
Protective tubing length L: 35cm.
Lead wire type: Standard.
Lead wire length M : 1m.
A Wide Variety of High-precision.
Temperature Sensors.
by new models with ferrules to help reduce wiring work.
Ideal for the thermal input devices of Temperature Controllers.
and also according to the type and shape of the terminal.
Case color: Black.
Control output: Voltage output (for driving SSR).
Control mode *1: Standard or heating/cooling.
No. of auxiliary outputs: 1.
Detection of heater burnout, SSR failure, and heater overcurrent: --.
No. of event inputs: --.
Transfer output *2: --.
Communi cations: RS-232C.
Previous model: Thermocouple input, --;
Resistance thermometer input, -- OMRON E52-CA35AY D=6.4 1M.
New 48 x 24-mm Basic Temperature,
Controller with Enhanced Functions and,
Performance
E52-CA35AY D=6.4 1M Improved Indication Accuracy,
and Preventive Maintenance Function.
Indication Accuracy.
Thermocouple input: ±0.3% of PV (previous models: ±0.5%),
Pt input: ±0.2% of PV (previous models: ±0.5%),
Analog input: ±0.2% FS (previous models: ±0 OMRON E52-CA35AY D=6.4 1M. 5%),
Models are available with screw terminal blocks or screwless,
clamp terminal blocks.
A PV/SV-status display function can be set to automatically alternate,
between displaying the status of the Temperature Controller (auto/
manual, RUN/STOP, and alarms) and the PV or SV.
Preventive maintenance for relays in the Temperature,
Controller using a Control Output ON/OFF Counter.
Switch the PV display between three colors OMRON E52-CA35AY D=6.4 1M.
Compatible with Support Software (CX-Thermo version 4.2 or higher).
Eleven-segment displays.
Models are available with one or two alarm outputs. Size: 48 x 96mm.
Type: power AC/DC24V with.
Shell color: silver.
Control output 1: output unit mode.
Control output 2: output unit mode.
Control mode: standard or heating cooling.
Auxiliary output points: 2 points.
The detection function of the broken wire and SSR fault of heater: detection function of single phase or three phase heater.
Event entry point: 2.
Transfer output: -.
Remote SP:4 to 20mA input.
Communication: RS-422.
General thermostat new high performance (high resolution, high speed, high precision input) type products.
Support simple operation, preventive maintenance.
A new type of liquid crystal, which can communicate with the front through the infrared port, is adopted,
Visual angle, contrast can be improved.
High resolution 5 bit display / can display 0.01 degrees C.
High speed sampling period 60ms.
All models complete a variety of (to the thermocouple /Pt/ analog input switching), 1 machines to support a variety of sensors.
Also supports remote SP.
Add PV/SV status display function, convenient to check thhe state of the thermostat (automatic / manual, RUN/STOP, alarm),
Interactive display PV/SV E52-CA35AY D=6.4 1M.
By supporting software (Ver.4.0 CX-Thermo) to carry out a simple function (AND/OR logic and delay),
Be able to execute flexible contact output E52-CA35AY D=6.4 1M.
Increase the control output ON/OFF number counting function, can predict the temperature controller internal relay fault.
Position ratio type.