Unit classification: CJ1 Special I/O Units.
Product name: ProcessInput Units,
(Isolated-type Thermocouple Input Units).
Input points: 4 inputs.
Signal range selection: Common inputs.
Signal range: Thermocouple: R, S, K, J, T, L, B.
Conversion speed (resolution): Conversion,
speed: 250 ms/4 inputs CS1G-CPU42-V1 PROGRAMMING MANUAL.
Accuracy at ambient temperature of 25°C:
Accuracy: (±0
CS1G-CPU42-V13% of PV or ±1°C,
whichever is larger) ±1 digit max.
External connection: Removable terminal block.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0.25A; 24V, --.
Standards: UC1, CE.
A Single Unit Handling All Types of Inputs,
such as Temperature Sensor Inputs and,
Analog Signal Inputs (e.g., 4 to 20 mA or 1 to 5V) CS1G-CPU42-V1 PROGRAMMING MANUAL.
A Unit supports four input channels,
each of which can be set to a
platinum resistance thermometer, thermocouple,
and DC signal (current, voltage).
All inputs are isolated. Unit type: CS1 Basic I/O Units.
Product name: Triac Output Units.
Specifications: 250 VAC, 2 A max.
8 outputs.
Mountable Racks: CPU Rack, CS1W-BC,
@@3, Yes, @@2, Yes;
C200HX/HG/HE Expansion I/O Rack, No CS1G-CPU42-V1 PROGRAMMING MANUAL.
CS1 Expansion Rack, CS1W-BI,
@@3, Yes, @@2, Yes;
CS1 Long distance Expansion Rack, Yes;
SYSMAC BUS Slave Rack, No.
Words required: 1 word.
Current consumption: 5V system, 0.23 max.
(0.07+0.02 ×number of ON points);
26 V system, --.
(0.07+0.02 ×number of ON points).
Standards: UC, N, L, CE.
Multi-application Controllers:
From High-performance Machine C,
Highly Reliable Process Control.Unit type: CS1 Special analog I/O Units.
Product name: Analog Output Units.
Specifications: I/O points, 8 outputs;
Signal range selection,
Set separately for each input;
Signal range, 4 to 20 mA;
Resolution, 1/4000 ;
Conversion speed, 1 s/point CS1G-CPU42-V1 Manual.
Externa connection, Removable erminal block.
Current consumption: 5V, 0.13A; 26V, 0.25A.
Standards: UC1, N, CE.
For Various Analog I/Os.
Anaalog Input Units for converting,
analog input signals into binary data CS1G-CPU42-V1 Manual.
Analog Output Units for converting ,
binary data into analog output signals.