Appearance: Rectangular (M16-J).
Lighting: LED without Voltage Reduction Unit, 12 VAC/VDC.
Degree of protection: IP40.
Display color symbol: R: red; Y: yellow; G: green; A: blue;
W: white; PY: pure yellow; PW: pure white.
Cylindrical 16-dia. Indicator.
Same basic design as the A16 Pushbutton Switch. Contact form: SPST-NO.
Type: Models with Built-in Operation Indicators.
Rated voltage: AC: 24, 100, 110, 120, 200, 220, 230, 240;
DC: 12, 24, 48, 110, 220
E6D-CWZ1E 800 P/R 0.5M
MK-S-series Relays with DC-switching,
Models That Can Switch 220 VDC, 10 A,
(Resistive Load).
Switch a DC load of 220 VDC, 10 A (resistive load).
Models for AC Loads can switch 250 VAC, 15 A (resistive load).
Lineup includes models with SPST-NO and SPST-NO/SPST,
NC contact forms.
Using a SPST-NO/SPST-NC contact form enables detecting,
contact welding. (When the NO contacts become welded, the,
NC contacts will maintain a minimum distance of 0.5 mm.).
Models available with operation indicators and built-in test buttons.
RoHS compliant.
Standards: UL, IEC (TÜV certification). Classification: LED indicator.
Coil ratings: AC 24, 110, 120, 230, 240; DC 6, 12, 24, 48.
Contact form: SPDT.
Slim and Space-saving Power Plug-in Relay.
Reduces wiring work by 60% when combined with the,
P2RF-@-PU Push-In Plus Socket.
(according to actual OMRON measurements).
Lockable test button models available.
Built-in mechanical operation indicator.
Provided with nameplate.
AC type is equipped with a coil-disconnection self-diagnostic,
function (LED type).
High switching power (1-pole: 10 A). Case color: Black.
Control output: Current output.
Control mode *1: Standard or heating/cooling.
No. of auxiliary outputs: 1.
Detection of heater burnout, SSR failure, and heater overcurrent: --.
No. of event inputs: 2.
Transfer output *2: Transfer output using control output.
Communi cations: --.
Previous model: Thermocouple input, --;
Resistance thermometer input, --.
New 48 x 24-mm Basic Temperature,
Controller with Enhanced Functions and,
Performance. Improved Indication Accuracy,
and Preventive Maintenance Function.
Indication Accuracy.
Thermocouple input: ±0.3% of PV (previous models: ±0.5%),
Pt input: ±0.2% of PV (previous models: ±0.5%),
Analog input: ±0.2% FS (previous models: ±0.5%),
Models are available with screw terminal blocks or screwless,
clamp terminal blocks.
A PV/SV-status display function can be set to automatically alternate,
between displaying the status of the Temperature Controller (auto/
manual, RUN/STOP, and alarms) and the PV or SV.
Preventive maintenance for relays in the Temperature,
Controller using a Control Output ON/OFF Counter.
Switch the PV display between three colors.
Compatible with Support Software (CX-Thermo version 4.2 or higher).
Eleven-segment displays.
Models are available with one or two alarm outputs.
E6D-CWZ1E 800 P/R 0.5M Operation manual / Instructions / Catalog download link:
/searchDownload.html?Search=E6D-CWZ1E 800 P/R 0.5M&select=5