Connecting I/O control module and interface module.
Cable length: 0.3 m.Input capacity: 16 points.
Mounted relays: NY-5W-K-IE (Fujitsu Component).
Rated load: Resistance load,
250 VAC 2 A/output, common 8 A,
30 VDC 2 A/output, common 8 A.
Rated ON current: 3 A/output.
Maximum contact voltage: 250 VAC, 125 VDC.
Maximum contact current: 3 A/output.
Maximum switching capacity: 750 VAAC, 90 WDC
G3NE-210T DC12
Minimum applicable load(reference value): 5 VDC 1mA.
Mechanical service life: 20,000,000 operations min.
Electrical service life: 100,000 operations min.
Number of circuits per common: 8 points/common.
Output indicators: LED display (yellow).
Isolation method: Relay isolation.
I/O power supply method: The relay drive power,
is supplied from the unit power supply.
Unit power supply current consumption:
210 mA max. (for 20.4 to 26.4-VDC power supply voltage).
Weight: 290 g max.
Expansion functions: Enabled.
Output handling for communica tions errors:
Select either hold or clear.
Short-circuit protection function: No.
High-speed digital I/O terminal with the,
screw type terminal block for EtherCAT,
communications.
Detachable screw terminal block facilitates,
the maintenance.
The expansion unit can be connected.
(One expansion unit per one I/O terminal unit.)
Input/output point can be flexibly increased,
depending on the system.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification becomes,
possible for maintenance. Connects Power Supply Adapter and SYSMAC NET Link Unit.
For 1 Unit.Appearance: Square/Projection type LED lighting,
(without Voltage Reduction Unit) A22L-D.
Output: SPST-NO.
Lighting: LED.
Operating voltage: 24 VAC/VDC.
Operation: Alternate operation (self-holding).
Illumination color: R (red); Y (yellow); G (green); W (white); A (blue).
Install in 22-dia. or 25-dia. Panel Cutout.
(When Using a Ring).
Lever for easily mounting and removing the Switch Unit.
Increase wiring efficiency with three-row mounting of Switch Blocks.
Finger protection mechanism on Switch Unit provided as a standard feature.
Use 25-dia. ring to install in 25-dia. panel cutouts.
Mounted using either open-type (fork-type) or closed-type.
(round-type) crimp terminals.
IP65 oil resistance (non-lighted models).
IP65 (lighted models).
G3NE-210T DC12 Operation manual / Instructions / Catalog download link:
/searchDownload.html?Search=G3NE-210T DC12&select=5