Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min.
(between each input terminal and the G terminal)
OFF voltage: 5 VDC max.
(between each input terminal and the G terminal)
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC);
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms, 1 ms,
2 ms, 4 ms, 8 ms, 16 ms, 32 ms (Default setting: 1 ms)
D4B-1187N
Number of circuits per common: 16 inputs/common.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current con sumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 180 g max.
Expansion functions: Enabled.
Short-circuit protection function: No.
High-speed digital I/O terminal with the,
screw type terminal block for EtherCAT,
communications.
Detachable screw terminal block facilitates,
the maintenance.
The expansion unit can be connected.
(One expansion unit per one I/O terminal unit.)
Input/output point can be flexibly increased,
depending on the system.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification becomes,
possible for maintenance. Size: 48 x 96mm.
Control output 1: current.
Auxiliary (alarm) output: 4.
Transfer output: -.
Event input: 2.
Communication: RS-485.
Disconnection detection: 1.
Power supply voltage: DC24V/AC24V.
E5 - C series of new products program.
Maximum 256 segment of the program capacity,
Support for multiple applications.
Can be set up to 8 procedures (mode) x 32 (step) procedure.
The use of high 25mm (E5AC-T), 18mm (E5AC-T) PV display (white),
Improve visibility.
Not only on the top of the body, but also on the front,
The use of communication adapter cable (sold separately) connected to the computer after,
No power connection can be set.
It can be easily set by CX-Thermo (sold separately).
High speed sampling to achieve 50ms.
With auxiliary output (4 points), event input (maximum 6 points), the transmission output,
Support a variety of applications.
Slender fuselage depth 60mm.
Easy to connect with PLC through no program communication.
Combined temperature control device through component communication.
Add position proportional control type, also support control valve control.
D4B-1187N Operation manual / Instructions / Catalog download link:
/searchDownload.html?Search=D4B-1187N&select=5