Insulation method: Photocoupler.
Operation indicator: Yes.
Response speed: Low-speed.
Applicable load: 4 to 32 VDC 0.1 to 100 mA.
Input rated voltage: 12 to 24 VDC.
SSR with Plug-in Terminals.
The Same Shape as the G2R-1-S.
Power Relays.
These I/O solid state relays can be mounted in OMRON.
G70A I/O Terminals GRT1-DRT REFERENCE MANUAL.
Lineup includes Input Modules for microloads and Output,
Modules for standard loads
GRT1-DRT
Lineup also includes UL, CSA, and TÜV-certified models,
(-UTU models). Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min.
(between each input terminal and the G terminal)
OFF voltage: 5 VDC max.
(between each input terminal and the G terminal)
OFF current: 1.0 mA max GRT1-DRT REFERENCE MANUAL.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms, 1 ms,
2 ms, 4 ms, 8 ms, 16 ms, 32 ms. (Default setting: 1 ms)
Number of circuits per common: 8 points/common.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply GRT1-DRT REFERENCE MANUAL.
Input device supply current: 100 mA/point.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current consumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 370 g max.
Expansion functions: No.
Short-circuit protection function: No.
A common terminal is provided for each contact.
It eliminate the needs for relay terminal blocks.
It is unnecessary to share the common terminal,
among multiple contacts.
Easy-to-find wiring locations.
Detachable screw terminal block facilitates the maintenance.
Input response time can be switched for high-speed processing.
Selectable node address setting methods: setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch, setting is easy and,
node identification becomes possible for maintenance. Name: CompoNet Gateway Unit for CC-Link.
Specifications: CC-Link Communications,
Specification, Station Type,
Remote device stations;
Number of stations occupied: 4.
CC-Link Version: Version 1.10 or 2.00.
(Selected using mode switch.);
CompoNet Communications Specification,
communications Types of,
Remote I/O Communications;
Maximum I/O capacit, Word Slave Units:
2,048 I/O points total(1,024 inputs and,
1,024 outputs)Bit Slave Units:
512 I/O points total.
(256 inputs and 256 outputs)
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring material costt can be reduced GRT1-DRT Manual.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on sitee GRT1-DRT Manual.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error.