The unit comes with coaxial type.Unit type: CJ1 Basic I/O Units.
Product name: DC Input Units.
Specifications: I/O points, 16 inputs(High speed);
Input voltage and current: 24 VDC, 7 mA;
Commons, 16 points, 1 common; External connection,
Removable terminal block; No. of words allocated, 1 word C200HG-CPU53-ZE OPERATION MANUAL.
Current consumption: 5V, 0.13A; 24V, --.
Standards: N, L, CE
C200HG-CPU53-ZE
A Wide Range of Basic Input,
Units for High Speed Input and,
Different Applications.
Receive ON/OFF signals from external,
devices into the PLC System to update,
I/O memory in the CPU Unit.
New high-speed input models CJ1W-ID212 and,
CJ1W-ID233 are now available. These units can,
help to increase system throughput.
Name: Clamp Terminal Blocks C200HG-CPU53-ZE OPERATION MANUAL.
Specifications: Inputs; 8 inputs ; NPN; --.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring material cost can be reduced.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on site C200HG-CPU53-ZE OPERATION MANUAL.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error. Unit type: CS-series Special I/O Units.
Product name: Analog Input Units.
Specifications: I/O points, 4 inputs;
Signal range selection,
Set separately for each input;
Signal range, 1 to 5 V, 0 to 5 V,
0 to 10 V, -10 V to 10 V, 4 to 20 mA;
Resolution, 1/8,000 (Settable to 1/4,000);
Conversion speed, 250 s/point max.
(Settable to 1 ms/point).
Externa connection, Removable terminal block.
Current consumption: 5V, 0.12A; 26V, 0.09A.
Standards: UC1, N, CE.
For Various Analog I/Os.
Analog Input Units for converting,
analog input signals into binary data.
Analog Output Units for converting ,
binary data into analog output signals. Unit type: CS1 Special I/O Units.
Product name: Isolated-type,
2-Wire Transmitter Input Unit.
Input points : 4 inputs.
Signal range: 4 to 20 mA, 1 to 5 V.
Conversion speed (resolution):
100ms/4 inputs.
Externa connection: Removable erminal block.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0.15A; 26V, 0.16A.
Standards: UC1, CE.
Provides the functionality of isolators,
power supplies, signal converters,
and other devices.
The Analog Input Unit converts analog,
input signals such as 1 to 5 V or 4 to 20mA,
into digital values, and takes the values,
scaled in industrial units, and transfers,
it to the CPU Unit as the process value.
Because of this, no ladder program is required,
at the CPU Unit for scaling.
The Analog Output Unit converts analog output set,
values from the CPU Unit to analog output signals,
such as 4 to 20 mA or 1 to 5 V, and outputs them.
The built-in functions, such as measurement value,
alarms, rate-of-change calculations, and square roots,
have enabled major savings in cost and space coompared,
with previous systems C200HG-CPU53-ZE Manual.
High-resolution Models and 8-point Input Models are,
also available.
By combining the Units, logging/monitoring.
systems can be constructed,
or the Units can be used together with LCBs/LCCUs,
to construct complete process control systems C200HG-CPU53-ZE Manual.
Parameters can be easily displayed and set in an,
easy-to-understand form without special tools.