Control supply voltage: 110/220 VAC; With voltage fluctuation compensation.
Operating current: 1 to 2 A.
Accurate Detection of Heater Element.
Burnout Regardless of Heater Capacities.
Accurately detects a burned heater element or elements incor,
porated by a molding machine or packing machine and outputs,
an alarm signal K8AB-AS3 AC100/115V PDF datasheet.
Precisely singles out the burned element even if one heater el,
ement among several heater elements has been burned out
K8AB-AS3 AC100/115V
Applicable to small- to large-capacity heater elements.
All K2CU-F large-capacity, built-in current transformer models,
work with both single-phase and three-phase heaters.
Voltage fluctuation compensation function eliminates false,
alarms due to variations in the supply voltage K8AB-AS3 AC100/115V PDF datasheet. Input type: DC current input.
Output type: BCD+ transistor; -; NPN open collector (5 bit output +HH, PASS, L, LL).
Event input terminal 5 points (TIMING, S-TIM, HOLD, RESET, ZERO) is equipped with.
External supply 80mA DC12V.
Power supply voltage: AC100 ~ 240V.
96 (W) * 48 (H * 95mm) depth
Some models are not equipped with.
The most suitable voltage and current signal simulation, measurement and display, identification of the panel table K8AB-AS3 AC100/115V PDF datasheet.
Action determine the color, can switch the green / Red 2 kinds of color display.
Equipped with the sub pressure gauge for monitoring the operation trend.
External event input can be applied to a variety of measurement and identification situations.
DMeasuring current: 10 to 100 A AC, 20 to 200 A (See note.).
Supply voltage: 100-115 VAC.
Ideal for current monitoring for,
industrial facilities and equipment.
Monitor for overcurrents or undercurrents.
Manual resetting and automatically resetting supported by one Relay.
Startup lock and operatiing time can be set separately K8AB-AS3 AC100/115V datasheet PDF catalog.
One SPDT output relay, 6 A at 250 VAC (resistive load).
Output relay can be switched between normally open and,
normally closed.
Process control signal (4 to 20 mA) and coommercial CT input,
(0 to 1 A or 0 to 5 A) supported K8AB-AS3 AC100/115V datasheet PDF catalog.
Output status can be monitored using LED indicator.
Inputs are isolated from the power supply.