Isolation method: Relay.
Zero cross function: No.
Operation indicator: Yes.
Applicable output load(See note.): 5 A 100 to 240 VAC.
Rated input voltage: 24 VDC.
Hybridization of a Magnetic Relay and an,
SSR Achieves 10-A Switching for 10 Million,
Operations.
UL/CSA certified (-VD models).
Using a triac to open and close the circuit reduces chattering,
and arching, thereby increasing the electrical durability to 10,
million operations G3RV-SR700-D AC200 PDF datasheet
G3RV-SR700-D AC200
Relays contacts for power ON and 10-A switching with high,
capacity are provided in a compact body without the need of,
radiators. Plus, there is almost no effect on heat generation,
or ambient temperature.
Operation indicators to easily check operation G3RV-SR700-D AC200 PDF datasheet.
Built-in temperature fuse prevents internal burning due to,
triac or relay malfunctions.
Socket-type Relays the same size as the 1-pole and 2-pole,
LY Relays. Terminal (Wire connection): Push-In Plus Terminal.
Classification: Microloads.
Latching lever (Test switch): No.
Rated input voltage: AC, 110V.
Global standard size, low profile slim.
I/O relay with width 6.2 mm.
Realized about 25% lower profile than conventional G3RV-SR700-D AC200 PDF datasheet.
products, contributing to further miniaturization of the control panel.
Realized opening and closing ability with one pole 6 A slim shape.
Micro load products for one pole 50 mA using Au-plated.
contacts for small load switching also available.
Since G2RV is a transparent case, confirming the state of,
the contact with the naked eye is possible, and easy to,
confirm abnormality on-site (installed location).
Screw terminal is also stocked to meet the screw type needs.
Mounted relay uses plug-in terminals that are difficult to,
bend when exchanging. Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min.
(between each input terminal and the G terminal)
OFF voltage: 5 VDC max.
(between each input terminal and the G terminal)
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC);
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms, 1 ms,
2 ms, 4 ms, 8 ms, 16 ms, 32 ms (Default setting: 1 ms).
Number of circuits per common: 16 inputs/common.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current con sumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 180 g max.
Expansion functions: Enabled.
Short-circuit protection function: No.
High-speed digital I/O terminal with the,
screw type terminal block for EtherCAT,
communications.
Detachable screw terminal block facilitates,
the maintenance.
The expansion unit can be connected.
(One expansion unit per one I/O terminal uunit G3RV-SR700-D AC200 datasheet PDF catalog. )
Input/output point can be flexibly increased,
depending on the system.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary sswitch and with tool software G3RV-SR700-D AC200 datasheet PDF catalog.
When setting the nodes with rotary switch,
setting is easy and node identification becomes,