Main contacts: 3PST-NO.
OFF-delay contacts: DPST-NO.
Auxiliary contact: SPST-NC.
Number of input channels: 1 channel or 2 channels possible.
OFF-delay time: 15 s.
Rated voltage: 24 VAC/VDC; 100 to 240 VAC.
The G9SA Series Offers a Complete.
Line-up of Compact Units.
Four kinds of 45-mm wide Units are available:
A 3-pole model, a 5-pole model, and models with 3 poles,
and 2 OFF-delay poles, as well as a Two-hand Controller G3PE-215B DC12-24 PDF datasheet
G3PE-215B DC12-24
Also available are 17.5-mm wide Expansion Units with 3,
poles and 3 OFF-delay poles.
Simple expansion connection.
OFF-delay models have 15-step OFF-delay settings.
Conforms to EN ISO13849-1 (PLe/Safety Category 4).
Both DIN track mounting and screw mounting are possible G3PE-215B DC12-24 PDF datasheet. Input capacity: 16 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min.
(between each input terminal and the V terminal)
OFF voltage: 5 VDC max.
(between each input terminal and the V terminal)
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0 G3PE-215B DC12-24 PDF datasheet. 5 ms, 1 ms,
2 ms, 4 ms, 8 ms, 16 ms, 32 ms. (Default setting: 1 ms)
Number of circuits per common: 8 points/common.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Input device supply current: 100 mA/point.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current consumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 370 g max.
Expansion functions: No.
Short-circuit protection function: No.
A common terminal is provided for each contact.
It eliminate the needs for relay terminal blocks.
It is unnecessary to share the common terminal,
among multiple contacts.
Easy-to-find wiring locations G3PE-215B DC12-24 datasheet PDF catalog.
Detachable screw terminal block facilitates the maintenance.
Input response time can be switched for high-speed processing.
Selectable node address setting methods: setting with rotary,
switch and with tool software G3PE-215B DC12-24 datasheet PDF catalog.
When setting the nodes with rotary switch, setting is easy and,
node identification becomes possible for maintenance.