Cable with connector (1 to 2) /G79-O_C-_, G79-I_C-_.
L size: A, 3000mm; B, 2750mm.
Input use.
Cable and loose wire cable with loose wire pressing connecting terminal,
Connector cable, MITSUBISHI motor produced PLC connection cable. Input capacity: 16 points.
Rated current (ON current): 0.5 A/output,
4 GRT1 Series Safety Precautions. 0 A/common.
Internal I/O common: NPN.
Residual voltage: 1.2 V max
GRT1 Series
(0.5 ADC, between each output,
terminal and the G terminal)
Leakage current: 0.1 mA max.
ON delay: 0.5 ms max.
OFF delay: 1.5 ms max.
Number of circuits per common:
8 points/common.
Output indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply GRT1 Series Safety Precautions.
Output device supply current: 100 mA/point.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current consumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 370 g max.
Expansion functions: No.
Output handling for communications errors:
Select either hold or clear.
Short-circuit protection function: No.
A common terminal is provided for each contact GRT1 Series Safety Precautions.
It eliminate the needs for relay terminal blocks.
It is unnecessary to share the common terminal,
among multiple contacts.
Easy-to-find wiring locations.
Detachable screw terminal block facilitates the maintenance.
Input response time can be switched for high-speed processing.
Selectable node address setting methods: setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch, setting is easy and,
node identification becomes possible for maintenaance GRT1 Series Manual. Safety outputs *1: Instantaneous, 2 (Semi conductors); OFF-delayed*2, 0.
Auxiliary outputs *3: 2 (Semi conductors).
Logical AND connection input: 1.
Logical AND connection output: 1.
Max. OFF delay time *4: --.
Rated voltage: 24 VDC GRT1 Series Manual.
Terminal block type: Screw terminals.
Electronic Detection Mechanism for.
Better Stability in Non-contact Door.
Switch Operation.