Specifications: Twisted pair.CV500-CN Cable Bus Connecting Cable Used to join two Hard Disk Units CV500-CN116.
Name: CS1D CPU Unit for Single CPU Systems.
Specifications: Number of I/O points,
960 points (2 Racks);
Program capacity, 10 Ksteps;
Data Memory, 64 Kwords(DM: 32 Kwords,
EM: 32 Kwords×1 bank);
LD execution time, 0 CS1D-CPU42S.04 μs;
Duplex CPUs, --;
Interrupt functions, OK.
Current consumption: 5V system, 0.78A;
26V system, --.
Standards: UC1, N, L, CE
CS1D-CPU42S.
Redundant CPU Units , Power Supply Units ,
Communications Units ,
and Expansion I/O Cables. Unit type: CJ1 Special I/O Units.
Product name: Analog Output Unit.
I/O points: 2 outputs;
Signal range selection:
Set separately for each output CS1D-CPU42S.
Signal range, Resolution: 1 to 5 V,
0 to 5 V, 0 to 10 V, -10 to 10 V,
4 to 20 mA; 1/4,00.
Conversion period: 1 ms/point.
Accuracy at ambient temperature of 25°C:
Voltage: ±0.3% of F.S. Current: ±0.5% of F.S.
External connection: Removable terminal block OMRON CS1D-CPU42S.
External power supply: 24 VDC +10% -15%, 140mA max.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0.12A; 24V, 0.14*3.
Standards: UC1, N, L, CE.
Consistent Microsecond Throughput:
Models with Direct Conversion Join the Lineup.
Analog Input Units for converting analog input,
signals into binary data OMRON CS1D-CPU42S.
Analog Output Units for converting binary ,
data into analog output signals. Name: MIL Connectors.
Specifications: Outputs; 16 outputs ; PNP; --.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet OMRON CS1D-CPU42S.
Branching is easily made with CompoNet.
Wiring material cost can be reduced.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on site.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error. A Wide Range of Basic Mixed,
I/O Units for Different Applications,
and Wiring Methods.
One Mixed I/O Unit has connectors for,
both inputs and outputs.
Use Mixed I/O Units to easily ,
build space-saving systems CS1D-CPU42S. Number of analog inputs: 4 inputs.
Number of analog outputs: 2 outputs.
Input signal ranges: –10 to 10 V, 0 to 10 V, 0 to 5 V.
Output signal ranges: –10 to 10 V.